Honeywell wiring 7 min read

Honeywell VisionPRO 8000 Wiring: TH8321WF1001, U1 and K Wire

By Ismail Farooq Published 2026-11-11 • Updated 2026-11-11 • Based on Resideo’s VisionPRO 8000 Smart installation guide
In short:

The VisionPRO 8000 Smart (TH8321WF1001) requires a C wire. Its wallplate has two columns of letters: read Conventional for a furnace or boiler and Heat Pump for a heat pump, where the same screws become O/B, AUX-E and L/A. One power wire goes on R or Rc with the factory jumper left in; two transformers mean removing it. K is only for the C-wire adaptor, and the two U1 screws are a relay for a humidifier, dehumidifier, ventilator or one extra stage.

1. Which thermostat this covers

This article follows Resideo’s VisionPRO 8000 Smart installation guide (33-00065EFS-01, Rev. 06-20), written for model TH8321WF1001, the Wi-Fi VisionPRO 8000 sold through contractors under the Honeywell Home name. The RedLINK VisionPRO models (TH8321R, TH8320R, TH8110R) are not covered by this guide or this article. The short guide also says where the longer document lives: the product data sheet, with fuller diagrams, is on customer.resideo.com.

The wiring diagrams in the guide are all 24 V systems. If your old thermostat is wired to L1 and L2 with thick wires, read our line voltage thermostat guide first.

2. The terminals, column by column

The wallplate is printed with a Conventional column and a Heat Pump column. Several screws carry a different letter in each, which is the main source of confusion on this thermostat. Resideo’s “Terminal Designations” table reads:

ConventionalHeat pumpWhat Resideo says it is
CCCommon wire from the secondary side of the cooling transformer
RcRcCooling power
RRHeating power
WO/BHeat stage 1, or the changeover valve on a heat pump
W2AUX-EHeat stage 2, or backup heat and emergency heat on a heat pump
YYCompressor stage 1
Y2Y2Compressor stage 2
GGFan relay
AL/AEconomizer module or lighting panel (time of day); on a heat pump also the compressor monitor or zone panel
U1 / U1U1 / U1IAQ relay for humidification, dehumidification or ventilation, or a stage of heating or cooling
S1 / S1S1 / S1Input for a wired indoor, outdoor or discharge sensor
KKConnects to K on the C-wire adaptor

If your old thermostat has a letter that is not in this table, our terminal letter index says what each one usually means before you decide where it goes.

3. Power: C wire and the R-Rc jumper

The guide states the power rule twice: “24VAC power is required. Connect common side of transformer to C terminal”, and again at the wiring step, “24VAC (C wire) is required.” There is no battery option in the guide, so a missing common wire has to be solved before the thermostat goes on the wall. Our C wire page explains how to find an unused conductor at the furnace.

R and Rc come joined by a factory installed jumper. The guide’s rules for it:

  • One transformer: leave the jumper in. Every single-transformer diagram shows the power wire on Rc with “R+Rc joined by jumper”.
  • Two transformers: “Remove factory installed jumper for two transformer systems.” The heating transformer’s wire goes on R and the cooling transformer’s wire on Rc.
  • Common with two transformers: the “common connection must come from cooling transformer”.

Not sure whether you have one transformer or two? Our Rh and Rc page shows how to tell from the old thermostat.

4. Resideo’s diagrams as one table

The guide draws each system on its own. This table reads across four of the most common ones. Each cell is what the terminal connects to at the equipment.

Terminal1H/1C, 1 transformer2H/2C, 2 transformersHeat pump 2H/1C (with aux heat)Heat pump 3H/2C (with aux heat)
RcPowerPower, cooling transformerPowerPower
RJoined by jumperPower, heating transformer (jumper removed)Joined by jumperJoined by jumper
C24 VAC commonCommon from the cooling transformer24 VAC common24 VAC common
W / O/BHeat relayHeat relay 1Changeover valveChangeover valve
W2 / AUX-EEmptyHeat relay 2Auxiliary / emergency heat relayAuxiliary / emergency heat relay
YCompressor contactorCool relay 1Compressor relayCompressor 1 relay
Y2EmptyCool relay 2EmptyCompressor 2 relay
GFan relayFan relayFan relayFan relay
A / L/AEmptyEmptyEquipment monitor (L)Equipment monitor (L)
S1Optional outdoor or remote sensor, in every diagram

The guide also draws heat only (Rc, W, C), heat only with fan, cool only (Rc, Y, G, C), heat pumps without auxiliary heat (1H/1C and 2H/2C), and a Series 20 valve system, where the thermostat’s R, W and Y go to valve terminals “R”, “B” and “W”.

5. Wiring steps

  1. Turn off power to the heating and cooling system. The guide’s warning is to disconnect power before installation.
  2. Photograph the old wiring and label each wire by its terminal letter, not its colour. Our wire colour guide explains why colours cannot be trusted.
  3. Separate the wallplate. Older units have a button on top of the wallplate: press it and pull. Updated models have no button; pull evenly along the sides and bottom.
  4. Mount the wallplate with the supplied screws and anchors. Resideo gives the drill sizes: 3/16 inch for drywall, 7/32 inch for plaster.
  5. Connect power: the common side of the transformer to C, and the power wire to Rc (or R and Rc with the jumper removed for two transformers).
  6. Wire the rest from the column that matches your system, using the tables above.
  7. Mount the thermostat. Hinged models hook in at the bottom and snap shut; models without hinges push on evenly.
  8. Restore 24 VAC and follow the installer setup prompts on screen.

If the screen stays blank, check for 24 V between R and C before anything else. Our multimeter guide shows the test.

6. No C wire: the K terminal

K is not a general-purpose terminal. The guide’s footnote says the THP9045A1098 C-wire adaptor “is used on heat/cool systems when you only have four wires at the thermostat and you need a fifth wire for a common wire”. You use K in place of Y and G, on conventional or heat pump systems, so the fan and compressor are controlled through a single wire, and “the unused wire then becomes your common wire”. The adaptor at the equipment splits K back into Y and G; Resideo refers you to the THP9045 instructions for that side.

Because the trick combines Y and G, it needs a system that has both. Our K terminal and wire saver page shows the furnace-side connections, and the no C wire guide lists what to do when the adaptor does not fit your system.

7. Heat pumps: O/B, AUX-E and L

Read the Heat Pump column for these. The guide draws four heat pump systems, from 1H/1C up to 3H/2C, and three notes carry the rules:

  • O/B, changeover valve: “O/B set to control as either O or B in installer setup.” One terminal serves both valve types, so the wire from your old O or B terminal lands here and the setting decides when it is energized. Our O/B page explains the difference.
  • AUX-E: a single terminal labelled “Auxiliary/Emergency heat relay (Heat 2)”. The short guide shows one backup heat wire and does not draw separate Aux and E wires. If your old thermostat has both, check the product data sheet or ask your installer before joining them. See aux heat vs emergency heat for what each does.
  • L: “Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor when set to Heat, Cool, or Off).” Connect it only if your old thermostat had an L wire; our L, S and T page covers it.

The compressor stays on Y, a second compressor stage on Y2, and the fan on G. For the bigger picture of heat pump terminals across brands, see our heat pump thermostat wiring guide.

8. The U1 terminals

The two U1 screws are the two sides of one relay. Resideo shows four ways to use it:

  • Powered humidifier, dehumidifier or ventilator: the accessory has its own transformer, so the two U1 terminals simply switch that circuit. No jumper.
  • Non-powered humidifier, dehumidifier or ventilator: the accessory runs from the system transformer, so the guide shows a “field install jumper between R and U1”.
  • Dehumidification with low speed fan: the relay is wired to the equipment’s low speed fan input, and it can be set to normally open or normally closed in installer setup.
  • An extra stage: heat stage 3, cool stage 3, backup heat stage 2 for heat pumps, or geothermal radiant heat. Here the guide says the U1 terminals “are normally open dry contacts”, and you must install the field jumper if the stage is powered by the system transformer, but not if the stage has its own transformer.

The guide rates U1 at 30 VAC maximum and 0.50 A. If nothing was connected to a U terminal or an accessory on your old thermostat, leave both U1 screws empty.

9. Installer setup and test

On first power-up the thermostat asks a series of questions: residential or commercial application, a thermostat name, programmable or not, temperature scale, whether to use an outdoor temperature (wired sensor or internet), and the type of heating system. The answers must match the wiring: a wire on O/B means choosing a heat pump, and that is also where O or B is set.

To go back in later, touch Menu, then Installer Options, enter the password and choose Installer Setup or Installer Test. The password is the date code, printed on the back of the thermostat and shown under Menu, Dealer Information. The Installer Test lets you perform an equipment test, which is the quickest way to confirm that every wire is on the right screw. Comparing models? The contractor-grade T10 Pro and T6 Pro use a different base with slider tabs instead of a jumper.

10. Frequently asked questions

Does the Honeywell VisionPRO 8000 need a C wire?

Yes. Resideo’s install guide for the TH8321WF1001 says “24VAC (C wire) is required” and tells you to connect the common side of the transformer to the C terminal. With only four wires on a heating and cooling system, the guide points to the THP9045A1098 C-wire adaptor, which uses the K terminal in place of Y and G so the freed wire can become C. Our no C wire guide covers the other options.

What are the U1 terminals on a VisionPRO 8000?

A relay with two terminals, both labelled U1. Resideo’s terminal table describes it as an IAQ relay for humidification, dehumidification or ventilation, or for one more stage of heating or cooling. When it runs a stage, the guide says the contacts are normally open and dry, and a jumper from R to U1 is fitted in the field only if that stage is powered by the system transformer.

Why does the VisionPRO 8000 wallplate have two sets of letters?

One column is for conventional systems and the other for heat pumps, and some screws change name between them. The screw marked W in the conventional column is O/B in the heat pump column, W2 is AUX-E, and A is L/A. Read the column that matches your equipment. Our terminal letter index explains each letter.

Where does the heat pump reversing valve wire go?

On O/B. The heat pump diagrams in the guide label it “Changeover valve” with the note “O/B set to control as either O or B in installer setup”, so the same terminal serves both valve types and the choice is made on screen. Our O/B terminal page shows how to tell which type you have.

What is the installer password on a TH8321WF1001?

The date code. The guide says it is printed on the back of the thermostat, and it can also be read on screen under Menu, Dealer Information, at the bottom of the list. You need it to reopen Installer Setup or run the Installer Test from Menu, Installer Options.